What winter here does to a heat pump
Heat runs eight months a year in this county, October through May. Cooling runs three, June through August. Whatever you install spends most of its life heating this house, so that side of the job matters more.
The overnight low here averages 19°F across December, January and February. A standard heat pump starts falling short of its rated output once it is below 40°F outside, and it often needs backup heat once it is below about 35°F. Nineteen degrees is under both marks. About 150 nights a year here hit freezing or below, over half the nights in the heating season, and every one of them sits under both marks too. A standard heat pump spends a lot of this winter working below its rating.
That does not rule out a heat pump here, it rules out the standard kind. A cold-climate heat pump is built and tested for this. To carry the ENERGY STAR Cold Climate label, it has to make at least 1.75 units of heat for every unit of electricity at 5°F, and hold on to 70 percent of its 47°F capacity at that temperature, verified by outside testing. In a two-winter field test of these in occupied homes, backup heat covered only a small share of the load between 0°F and 35°F, and running on backup alone was rare even above 0°F. This county only sees 0°F or below about 10 nights a year, a small part of the roughly 150 nights that hit freezing. A cold-climate heat pump is built for a winter that looks like this one.